Источники бесперебойного питания
| Категория реферата: Рефераты по информатике, программированию
| Теги реферата: деньги реферат, конспект по математике
| Добавил(а) на сайт: Budaev.
Предыдущая страница реферата | 1 2 3 4 5 6 | Следующая страница реферата
3.3.4 Tripp-Lite SmartPro Cable
Tripp-Lite Part# 73-0743 (SmartPro UPS) , Software: PowerAlert
[pic]
3.4 Neuhaus Distribution Group
3.4.1 Neuhaus SmartLine-420, SmartLine-750 (Fenton PowerPal)
Software: RUPS-II , Cable Part# M2502
[pic]
3.4.2 Neuhaus SmartLine/Fenton PowerPal interface pinout:
|Pi|Signal Type |
|n | |
|# | |
|1 |N/A |
|2 |AC Failure (Contact Closure) |
|3 |N/A |
|4 |Common |
|5 |Battery Low (Contact Closure) |
|6 |Rx (RS232) and Turn Off UPS (Contact |
| |Closure) |
|7 |Common |
|8 |N/A |
|9 |Tx (RS232) |
The contact closure signals are relay signals and are "normal open".
The RS232 signals are photo-transistor signals.
3.5 Para Systems Inc.
3.5.1 MinuteMan A-series DB-9 Interface Port
|P|Signal Type |
|i| |
|n| |
|#| |
|1|Unused |
|2|AC Failure |
|3|Unused |
|4|Common (same as 7) |
|5|Low Battery |
|6|RS-232 level shutdown |
|7|Common (same as 4) |
|8|Ground level shutdown (not available on |
| |models smaller than A500) |
|9|Reserved |
Pins 2 and 5 are connected to Common when they are true.
On pin 6, an rs-232 high level (>9V) will shutdown, when running on battery.
On pin 8, shorting to ground will shutdown.
3.6 PowerCom
3.6.1 PowerCom King UPS cable Software - UPSMon-II
[pic]
AC_Fail and Bat_Low - normally open (shorted to GND when active).
3.7 Exide/Deltec/Fiskars
3.7.1 Fiskars PowerRite Max / PowerRite Pro Cable
[pic]
3.7.2 Fiskars PowerRite UPS Port Configuration Table
|Pin #|Signal Type |Function |
|1 |Basic Modem Mode; |Remote UPS off: In presence|
| |Input: RS232 high pulse 4 |of AC, Output will turn |
| |to 5 seconds wide |off for 15 seconds after |
| | |conditionaldelay. In |
| | |absence of AC, output is |
| | |kept off until normal AC |
| | |returns |
|1 |Serial Data Mode; |RS232 serial communication |
| |Input: RS232 data |input. 1200 baud, 8-bit, no|
| | |parity, one stop bit, one |
| | |start bit, Xon/Xoff |
|2 |Basic Mode; |AC Input failure |
| |Output: RS232 level high | |
|2 |Serial Data Mode; |RS232 serial communication |
| |Output: RS232 data |output. Same as input |
|3 |Output: Open collector |AC Input failure |
| |transistor ON, 50 mA. 40 | |
| |VDC rating | |
|4 |Signal Common |Signal Common |
|5 |Output: Open collector |Impending low battery |
| |transistor ON. SO mA. 40 | |
| |VDC rating | |
|6 |Input: RS232 level low |Plug and Play software |
| |(-12V) |enable trigger |
|7 |Input: Relay contact or |Remote output OFF/ON: UPS |
| |RS232 level |total output can be kept |
| | |off with low signal or |
| | |closing relay contact |
|8 |Output: 8 to 25 VDC, 5 W |Auxiliary Control Power |
| |constant power (0.63 A | |
| |max. @ 8V) | |
|9 |Chassis |Connection to chassis |
3.8 Hewlett-Packard PowerWise
3.8.1 HP PowerWise L600/L900/L1250 interface pinout
|Pin|Signal |Function |
|# |Type | |
|1 |RS-232 |Signal Common for all RS-232 port signals |
| |Earth |(earth ground referenced) |
| |Ground | |
|2 |RS-232 |Serial communication mode - output signal |
| |Transmit |line. |
| |Output | |
|3 |RS-232 |Serial communication mode - input signal |
| |Receive |line. Contact Closure mode - shuts down UPS |
| |Input / |if signal is held high (RS-232 level) for 200|
| |Shutdown |milliseconds while UPS is operating in |
| | |battery mode. |
|4 |AC Line |Contact Closure mode - opened when AC line |
| |Fail |fails and UPS is operating in battery mode |
| |(normally |(breaks connection between Pin#4 and Pin#5). |
| |closed) | |
|5 |Contact |Signal Common for all Contact Closure group /|
| |Closure |RS-232 Signal Common line. |
| |Common / | |
| |RS-232 | |
| |Common | |
|7 |Low |Contact Closure mode - closed when remaining |
| |Battery |"on-battery runtime" drops below the |
| |(normally |under-defined time limit (makes connection |
| |open) |between Pin#7 and Pin#5). |
|9 |AC Line |Contact Closure mode - closed when in battery|
| |Fail |mode (makes connection between Pin#9 and |
| |(normally |Pin#5). |
| |open) | |
3.8.2 HP PowerWise L600/L900/L1250 cable
Hewlett-Packard Part# - 201-471-09 , Software - HP PowerWise Assistant
[pic]
Рекомендуем скачать другие рефераты по теме: мировая экономика, здоровый образ жизни реферат.
Категории:
Предыдущая страница реферата | 1 2 3 4 5 6 | Следующая страница реферата